AJ Power   1 Insight

If you would like to contact us here at AJ Power Limited. please feel free to do so by Post, Telephone and Fax, or Email.


InSight
InSight4000



Specsheets


If you would like to view the specifications of this series click the pdf below
Spec sheets are between 500kb - 2Mb.


InSight.pdf
InSight

 

  InSight is our exciting new range of generating set controls. The units have been meticulously designed using state-of-the-art technologies such as are employed in the mobile phone industry. In a similar manner, the units are compact in size and intuitive to use.

In addition to the features and functionality of conventional generating set control systems InSight offers the possibility of adding useful optional
features such as event recording and remote monitoring.
Automatic mains Failure panel, InSight5000 features:

LCD High resolution Monitor with brightness control displaying.

Instrumentation:
       Generator
Measure VL (line voltage) and VP (phase voltage)
Ammeter three phases
Frequency meter
Power factor indicator
Power (kVA, kW, kVAr)
Energy (kWh)
Start attempts
Hours run

Engine
Water temperature
Lubricating oil pressure
Battery Voltage

Mains
Measure VL (line voltage) and VP (phase voltage)
Ammeter

Control Functions
Automatic initiation of generating set from mains failure, phase failure, low voltage (programmable)
Remote initiation of generating set starting
Manual initiation of generating set starting
5 attempt starting programmable (start logic)
Automatic start/stop (AGE1) time/day/week timer programmable
Engine cool down timer

Protection:
Shutdowns for
Low oil pressure
High water temperature
Overspeed
Emergency stop operated
Fail to start
Alarms for
Low battery voltage
Battery charging system failure
Over/ under frequency protection (UF1)
Maintenance
Maintenance call alarm (MC1)
Record of alarm, shutdown activation, time, date up to 50 events (ER1)

Control Media
Configuration via panel soft keys
Configuration via PC (DPC cable / RS232)
Multi level password access
Emergency stop button control panel
Emergency stop button acoustic enclosure

Communications
CAN Interface terminals

Generator Monitoring
Monitor VL (line voltage) and VP (phase voltage)
Generator current 3 phases
Engine magnetic Pick up
Engine coolant temperature
Engine oil pressure
Battery voltage
Generator circuit breaker / contactor status

Mains Monitoring
Monitor VL (line voltage) and VP (phase voltage)
Mains current
Mains frequency
Mains circuit breaker / contactor status
Enable mains circuit breaker / contactor

Copyright AJ Power, 2008. All rights reserved. Website Design and Website Marketing by Rycoweb>